XZH TEST Completes 35kV Cable Fault Location in Gazipur, Bangladesh with Surge Method

2026-09-11

Najnowsze wiadomości o XZH TEST Completes 35kV Cable Fault Location in Gazipur, Bangladesh with Surge Method

A field service team has successfully located a high-resistance flashover fault on a 35kV underground power cable in Gazipur, Bangladesh, using time-domain reflectometry (the low-voltage pulse method) together with the high-voltage surge (direct flashover) method. The fault was pinpointed at 1,629.8 m from the test end on a cable whose measured full length was 1,896.2 m.

The cable under test was a 26/35kV three-core, 400 mm² XLPE power cable (YJV 3×400 26/35kV) serving a distribution circuit. A fault recording had shown a disturbance on phase B, prompting an on-site diagnostic campaign to determine the fault nature and distance before any excavation work began.

How the Fault Was Diagnosed

The testing followed a staged diagnostic procedure, beginning with insulation resistance measurement and moving to withstand voltage testing and pre-location once the fault nature was confirmed.

  1. The B phase was first measured to ground with an electronic megohmmeter on the 5kV range. The measured B-phase-to-ground resistance was 2.5 GΩ at 5,005V, indicating that the insulation appeared normal at low voltage, so a withstand voltage test was still required.
  2. A DC withstand voltage test was then performed using a 5/50 operating console and test transformer. When the B phase reached DC 40kV, a flashover breakdown discharge occurred at the fault point.
  3. Based on this behavior, the fault was classified as a phase-B flashover high-resistance fault.
Pre-Location Results

Two pre-location methods were applied: the low-voltage pulse method and the high-voltage direct flash (surge) method.

Using the low-voltage pulse method, the full length of the cable was measured at 1,896.2 m. The direct flash method was then applied; as the voltage rose to 40kV the fault point formed a flashover discharge, and the fault distance was determined to be 1,629.8 m from the test end.

ItemDetails
Project35kV power cable fault location field test
LocationGazipur, Dhaka Division, Bangladesh
DateAugust 27, 2026
Cable typeYJV 3×400 26/35kV XLPE power cable
Fault typePhase B flashover high-resistance fault
Marked cable length2,000 m
Measured cable length1,896.2 m
Fault distance1,629.8 m
Methods usedLow-voltage pulse method and high-voltage direct flash method
For very high flashover discharge faults of this type, sampling with the direct flash (surge) method is recommended, as it reliably reproduces the flashover and produces a clear reflected waveform for distance interpretation.
Key Takeaways
  • For extremely high flashover discharge faults, the direct flash method is the recommended sampling technique.
  • Most cable faults occur at joints, particularly on joints that have been in service for more than five years.
  • If the cable route is not clearly known, the route must be traced before accurate pinpointing is attempted.

This field case in Gazipur demonstrates a reliable, structured approach to diagnosing and pre-locating 35kV cable faults — combining insulation testing, withstand voltage testing and dual-method pre-location to deliver an accurate fault distance before excavation.

About XZH TEST: XZH TEST manufactures cable fault location and high-voltage testing equipment, including surge generators, cable fault pre-locators and VLF hipot testers. Its products support efficient fault pre-location, pinpointing and field diagnostics for power utilities, electrical contractors and testing organizations worldwide.