Factors Affecting the Accuracy of Transformer Winding Resistance Measurements

2026-11-19

Najnowsze wiadomości o Factors Affecting the Accuracy of Transformer Winding Resistance Measurements
Measurement Guide

Factors Affecting the Accuracy of Transformer Winding Resistance Measurements

Most wrong winding resistance readings are not instrument failures. They come from the connection, the temperature, or the moment someone pressed Save.

Reading time about 15 minutes | For transformer manufacturers, test engineers and maintenance teams

A winding resistance reading that is 3% high looks like a bad joint. A reading that keeps falling looks like a failing instrument. In practice, both are usually test conditions: a clip on a painted busbar, a winding that has not finished charging, or a temperature that was estimated instead of measured. This guide separates the factors that actually move the number.

Why this measurement is unforgiving

Winding resistance is one of several tests used to assess a transformer. It can provide evidence of poor welds and loose joints, contact problems in the tap changer, broken leads and broken strands in parallel conductors, and it can indicate short circuits between turns. It is rarely conclusive on its own: a shorted turn, a mechanical deformation and a bad tap contact can produce similar-looking deviations, which is why the result is read together with ratio, excitation current, short-circuit impedance and frequency response analysis.

First, a plain definition. A winding resistance test injects a steady DC current into a winding and measures the voltage drop across it; resistance is then calculated from Ohm's law. The test is simple in principle and demanding in execution, because the quantity being measured is tiny and the winding fights back.

Two consequences follow:

  • Small absolute errors matter. On a 1 mΩ winding, 10 µΩ of contact resistance is already 1%. A clip that would be fine for a continuity check is not fine here.
  • The reading is a comparison, not an absolute. Value comes from comparing phases, taps or the same unit over time. That is why repeatability - getting the same number twice under the same conditions - matters as much as accuracy.

Factor 1: the connection, and why four wires are not optional

The largest avoidable error in field measurement is lead and contact resistance. A two-wire measurement sends current through the same leads that sense voltage, so every clip, lug and centimetre of cable adds to the result.

Two-wire versus four-wire

R(measured) = R(winding) + 2 x R(lead) + R(contacts) [two-wire]

R(measured) = R(winding) [four-wire, within instrument accuracy]

In a four-wire (Kelvin) connection, the current leads carry the test current and the voltage leads sense only the drop across the winding. Because almost no current flows in the voltage circuit, lead resistance drops out of the result. The clamp must still make good contact, because the current path has to be stable, but its resistance no longer appears in the reading.

Where four-wire connections still go wrong

  • Voltage clip outside the current clip. The sense leads must sit inside the current path, directly on the winding or busbar being measured. Put them outside and the contact resistance comes back.
  • Clips on paint, oxide or grease. The instrument may show a stable number that is simply wrong. Clean the contact point down to bare metal.
  • Loose clips that heat. Resistance rises with temperature; a warm clip drifts during the test.
  • Long, thin current leads. They limit the available test current, which slows charging and reduces resolution on large windings.
  • Voltage leads routed beside power cables. They pick up noise. Keep them short, twisted where possible, and away from heavy current paths.

Factor 2: current stabilisation, not core saturation

A transformer winding is a large inductor. When the tester applies DC, current does not step to its final value; it rises gradually, and the displayed resistance falls while that happens. A reading taken during the rise is not a measurement, it is a snapshot of a transient.

This is often described as "waiting for the core to saturate". That description is misleading. What the measurement needs is a steady current, not a saturated core. Depending on the test current and the transformer design, the core may be far from saturation and the reading can still be perfectly valid. The magnetic state does matter, because it sets the effective inductance and therefore how long the current takes to settle, but saturation is not a pass condition.

Charging time constant, ideal RL circuit

tau = L / R and settling is roughly 5 x tau

Take a winding with L = 10 H and R = 0.5 Ω. Then tau = 20 s and the current is close to steady after about 100 s. This is a first-order approximation, not a fixed test duration: L varies with test current and core magnetisation, and a large power transformer can take much longer. It explains why proper testers show a charging state instead of a number, and why forcing an early reading produces a low value that looks like a fault.

Practical rules that follow from this:

  • Wait for the instrument to declare the reading stable, not for the display to look calm.
  • Treat "stable" as a criterion defined by the instrument or your procedure - commonly several consecutive samples inside a narrow band - rather than a fixed number of seconds.
  • For large units, expect several minutes per phase. Budget the outage time accordingly.
  • A higher test current magnetises the core further, usually lowering the effective inductance and shortening settling, but it also heats the winding. The two effects have to be balanced.
  • Some testers offer assisted excitation to shorten charging on low-voltage windings of large transformers; it changes the magnetic state, so use it only as the manufacturer permits and record it.

Factor 3: test current - enough to resolve, not enough to heat

Choosing a test current is a four-way compromise, not a single setting:

  • Winding resistance. Low-resistance windings need more current to produce a measurable voltage drop; high-resistance windings need less.
  • Rated current. Test current is normally a small fraction of rated current, because the winding must not be heated appreciably.
  • Instrument output. The tester must drive the selected current through the winding and lead loop; long or thin leads can make it unreachable.
  • Temperature rise. Copper rises about 0.39% per °C near room temperature, so a long high-current test changes the value it is measuring.

Two failure modes are common. Too low a current leaves the reading noisy and slow to settle, particularly on large windings. Too high a current shortens settling but heats the winding and may push the instrument out of its comfortable range.

If the test stays in "charging": first check the current loop - clips, lead continuity, lead length - then confirm the instrument can actually deliver the selected current into that resistance. Only then consider a different current setting. Changing the connection (for example, assisted excitation) is a separate decision that depends on the transformer connection and the manufacturer's instructions; it is not a general workaround.

Factor 4: temperature, the largest single error source

Resistance is a property of the conductor, and conductor resistance changes with temperature. Around 20 °C, copper changes by roughly 0.39% per °C; aluminium is similar at about 0.40% per °C. A 10 °C error in the assumed temperature produces about a 4% error in the result - larger than the accuracy of most instruments. These coefficients are approximations near ambient; over a wide temperature range the relationship is not perfectly linear.

Temperature correction to a reference temperature

R(ref) = R(t) x (K + T(ref)) / (K + t)

K is the inferred absolute-zero constant for the conductor material: 235 for copper and 225 for aluminium in the IEC convention used here. IEEE C57.12.90 commonly uses 234.5 for copper. Both are accepted, but the same constant must be used throughout a comparison, and the method should be stated in the report. T(ref) is the reference temperature required by your standard or specification - 75 °C is common for oil-immersed power transformers, but it is not universal; dry-type units use references tied to their insulation class, and some specifications call for a different value. Example: 0.500 Ω measured at 45 °C, corrected to 75 °C: R = 0.500 x (235 + 75) / (235 + 45) = 0.554 Ω, about 10.7% higher.

Which temperature is the right one

It is the winding temperature, not the ambient temperature and not automatically the top-oil temperature. After a transformer has been carrying load and is switched off, the winding is hotter than the oil, and the difference takes time to equalise. Two defensible methods:

  1. Use the winding temperature indication from the transformer's own measuring system - a winding temperature indicator, or a fibre-optic sensor where fitted - if it is available and its calibration is trusted.
  2. Use a stabilised oil temperature after the unit has cooled to thermal equilibrium, applying the correction or the waiting period that the applicable procedure specifies. Record that this was the method used.

Whichever method is used, apply it the same way every time and state it in the report. A consistent small bias is easier to interpret than a random one, and a change of method between tests can look like a change in the winding.

Factor 5: residual magnetism, offsets and test history

The core remembers. A previous DC test, a resistance measurement, or a normal shutdown can leave residual flux, and that changes how quickly the winding reaches a steady current. The symptom is a reading that settles at a different value than last time, or takes much longer to settle.

It is worth separating three things that are often confused:

  • Residual magnetism affects the inductance and therefore the settling behaviour. Where the manufacturer provides a demagnetisation procedure, follow it.
  • Thermoelectric EMF and offset appear as a small constant voltage, often from temperature differences between junctions. Reversing the current and averaging cancels it; this is a measurement technique, not a diagnosis of residual magnetism.
  • Instrument zero and lead effects are handled by the tester's compensation routines; check them first.

Do not conclude "residual magnetism" from a forward/reverse difference alone. A difference indicates an offset, and the cause of that offset needs its own investigation.

Factor 6: phase configuration and magnetic coupling

Windings in the same transformer are magnetically coupled. What you measure on one phase depends on how the other windings are left - open, shorted or grounded - and on whether the winding is star or delta connected.

  • Delta windings. The closed delta provides a parallel path through the other two limbs, so not all current passes through the winding you intended to measure. How much depends on the connection, lead arrangement and injection points; no single conversion formula fits every unit, so use the connection diagram and procedure.
  • Star windings. The neutral point and any links must be in the state the procedure requires.
  • Sequence matters. Measuring phases in the same order every time keeps the results comparable.
  • Assisted excitation. On YNd11 units with large-capacity transformers, where the available test current may be insufficient to charge a low-voltage winding quickly, some testers can apply magnetising current to another winding. The connection method and the permitted conditions come from the instrument manual and the transformer connection diagram; do not improvise them.

Factor 7: interference, grounding and the environment

Milliohm measurements compete with whatever else is happening in the substation: welding, DC stray currents, high-voltage fields and radio transmitters can all couple into the leads. Signs include a jumping last digit, a reading that changes when someone walks past, or a value that differs between morning and afternoon.

  • Ground the instrument case to a reliable earth point, as the manual requires.
  • Keep voltage leads away from current leads and from power cables; twist them if the run is long.
  • Use the instrument's averaging or filtering where available, and give it time to settle after switching nearby equipment.
  • Avoid testing while heavy loads are switching on the same station, if the schedule allows it.

Factor 8: instrument-side limits worth knowing

Modern winding resistance testers are accurate, but their specification has structure, and the structure matters at the bottom of a range. A typical statement is +/- (0.2% of reading + 2 digits) on the main ranges, widening to +/- (0.5% + 2 digits) at the top of the range, with a resolution of 0.1 µΩ.

The two terms behave differently. The percentage term scales with the reading; the digit term is fixed by the display resolution. At 1 mΩ on a 0.1 µΩ display, 0.2% is 2 µΩ and 2 digits is 0.2 µΩ, for a total of about 2.2 µΩ - roughly 0.22% of the reading. At 100 µΩ, the same 2 digits are 2% of the reading, which is why low-value measurements demand better connections and a suitable range.

  • Calibration status. An expired certificate does not make the instrument wrong, but it makes the result indefensible in an acceptance test.
  • Range boundaries. A reading at 5% of full scale carries more relative uncertainty than one at 50%.
  • Warm-up and supply. Battery state and ambient temperature affect the current source; a low battery can lengthen charging or trip the test.
  • Model-specific data. Accuracy, resolution and current ranges differ between models in a series. Use the datasheet for the exact unit in hand; do not transfer one model's numbers to another.

The error budget, in one table

SourceTypical effectHow to control it
Temperature assumed, not measuredAbout 0.4% per °C; a 10 °C error is about 4%Measure winding or stabilised oil temperature; correct to the stated reference
Two-wire connectionLead and contact resistance add directly; can rival the winding valueFour-wire connection, sense leads inside the current path
Reading taken before stabilisationSeveral percent low, variableWait for the instrument's stable indication
Contaminated or loose clipsUnpredictable, often unstableClean bare metal, re-clamp, check for heating
Test current heating the windingAbout 0.4% per °C riseShortest practical test, appropriate current range
Instrument accuracyPercentage of reading plus digits, per the datasheetValid calibration, range chosen for the value
InterferenceLast digits, occasionally moreGrounding, twisted leads, averaging, quiet station

A practical measurement sequence

  1. Record the transformer ID, tap position, winding connection and the temperature you will use for correction.
  2. Isolate the transformer and set the grounding state required by the approved test connection; the connection diagram and procedure define it, not a general rule.
  3. Clean the contact points and connect the four-wire lead set: current leads outside, voltage leads directly on the winding or busbar.
  4. Ground the instrument case; route voltage leads away from power cables.
  5. Select the current range for the expected resistance, considering the instrument's output capability and the winding's thermal limits.
  6. Start the test and wait for the stable indication; do not record intermediate values.
  7. Record resistance, temperature, current range, tap position and stabilisation time.
  8. Repeat on each phase and each required tap, in the same order every time.
  9. At the end of the test, follow the instrument's shutdown sequence: reduce the current, allow the discharge cycle to complete, and only then disconnect the leads in the order the manual specifies. Never open the current circuit while current is flowing.
  10. Correct all values to the reference temperature before comparing.

Reading the results: what counts as a problem

Once the numbers are corrected, the judgement is comparative. Three comparisons carry most of the information: phase to phase at the same tap, tap to tap across the range, and present values against the previous test or the factory baseline.

Phase imbalance

Imbalance(%) = (R(max) - R(min)) / R(average) x 100

A common field reference is that phase resistances should agree within about 2% after temperature correction. This is a reference example, not an acceptance criterion: the applicable standard, the transformer design, the connection and the customer specification decide the real limit, and different test procedures compare differently - some use the average of three phases, some compare pairwise, some compare against the factory record. A delta-connected winding also needs the conversion method that fits its connection before phases are compared.

Two habits prevent false alarms: compare like with like, and look at the trend before the absolute value. A winding that has moved 1.5% since the last test is more interesting than one sitting 1.5% from a nominal nameplate figure.

Troubleshooting: symptom, cause, action

SymptomLikely causeFirst action
Reading keeps fallingCurrent still rising; winding not stabilisedWait for the stable indication; check selected range
Reading drifts upward slowlyWinding heating; loose clip heating; ambient changeShorten the test, re-clamp, shade the set
Reading much higher than expectedTwo-wire connection, dirty contact, wrong tap, broken strandCheck lead arrangement, clean contacts, verify tap
One phase differs noticeablyTap contact, joint, or genuine winding faultRepeat the measurement; inspect joints; compare other taps and other tests
Display jumps in the last digitsInterference, long unshielded leads, poor groundGround the case, shorten or twist leads, use averaging
Test never completesCurrent cannot be driven through the loop; range too high; lead problemCheck current loop and lead continuity; confirm instrument output; then adjust range
Values differ from last year by a few percentTemperature reference or test conditions changedRe-correct to the same reference; compare recorded methods

Safety points specific to this test

  • A transformer winding stores magnetic energy. Never interrupt the current path while the test is running.
  • Follow the instrument's discharge sequence before touching or disconnecting leads. If supply is lost mid-test, observe the waiting period the manual specifies.
  • Do not operate the tap changer during measurement.
  • Ground the case and follow the site's isolation and tagging procedure; treat the winding as live until proved otherwise.
  • Keep the grounding arrangement exactly as the approved test connection requires; changing grounds during the test can create a hazard and corrupt the reading.

Key takeaways

  1. Use a four-wire connection; two-wire measurements add lead and contact resistance directly to the result.
  2. Wait for current stabilisation, not for core saturation. Settling follows L/R and can take minutes on large units.
  3. Temperature is the biggest single error source: about 0.4% per °C near ambient, so a 10 °C mistake is about 4%.
  4. Correct to a stated reference temperature before comparing anything, and keep the same reference and the same K constant throughout.
  5. Choose test current for adequate resolution and acceptable heating, within the instrument's output capability.
  6. Record connection, tap, temperature, method, range and stabilisation time; without them the number cannot be interpreted.
  7. Judge results by phase balance, tap comparison and trend - and treat winding resistance as one input, not a standalone verdict.

Frequently asked questions

Why does my winding resistance reading keep decreasing?

The winding is still charging. Current rises gradually in an inductive circuit, so the calculated resistance falls until the current stabilises. Wait for the instrument's stable indication. If the value never settles, check that the selected current range can actually drive the winding and that the current loop is sound.

How much does temperature really affect the result?

For copper, about 0.39% per °C near ambient; aluminium is similar. A 10 °C error in the assumed winding temperature gives roughly a 4% error, larger than the accuracy of most testers. Record the winding temperature, or a stabilised oil temperature, and state the method.

Can I use an ordinary two-wire multimeter for this test?

Not for diagnostic work. A two-wire meter adds lead and contact resistance to the reading, and those terms can be comparable to the winding resistance itself on large transformers. Four-wire measurement is the standard approach because it removes them; the sense leads must be connected inside the current path.

Why do the three phases differ by up to 2%?

Small differences are normal and come from winding geometry, tap position and test conditions. About 2% is a common field reference, not a universal acceptance limit; the standard, design, connection and customer specification set the real limit. A change since the last test usually matters more than the absolute spread.

Does a higher test current give a more accurate reading?

Not automatically. Higher current shortens charging and improves resolution on low-resistance windings, but it also heats the winding, and copper resistance rises with temperature. The right current gives a stable reading within an acceptable time without measurable heating, and it must be within the instrument's output capability. The manual defines the valid current and range combinations.

How long should I wait before recording a value?

Until the instrument indicates stability; that can range from seconds to several minutes. A fixed wait is not a safe substitute. Record the stabilisation time, because a sudden change in settling time is itself diagnostic.

Equipment referenced in this guide

Winding resistance testers

Related transformer diagnostic instruments (not winding resistance testers)

Checking a reading that does not look right?

Send the transformer rating, connection, tap position, measured values and the temperature you used. We will help you separate a measurement problem from a winding problem before you open the unit.

Scope note: this guide describes general practice for DC winding resistance measurement. Acceptance limits, temperature references, the K constant and connection methods come from the applicable standard, the transformer manufacturer's instructions and the customer specification. Values quoted here are typical examples, not universal requirements.